Description
We believe in: Innovation is our soul and spirit. Quality is our life. Customer need is our God for addressable fire alarm cable,afc fire alarm cable,aquaseal fire alarm cable, We sincerely welcome overseas customers to consult for the long-term cooperation and the mutual development.
NHXH-FE 180/E 90 Installation 4×1.5mm2 fire alarm safety Cable, Halogen-Free, 0.6/1 kV, With Improved Fire Characteristics
CABLE CONSTRUCTION
Conductor
|
Screen
|
Sheath Color
|
Solid bare Copper
IEC 60228 class 1 |
Aluminium laminated polyester tape | Red ( RAL 3000) or White |
Insulation
|
Earth Wire
|
Standard Packing Mode
|
Fire resistant silicon rubber (HD 22.1, BS 7655 EI2) | Tinned Copper to IEC 60228 Solid 0.80mm |
100 mtr / Plywood Reel 500 mtr / Plywood Reel (optional)
|
Insulation Colour
|
Sheath
|
|
2 Core: blue/brown | HFFR EN 50290-2,BS 7655 LTS1/LTS3 VDE 0207 |
ELECTRICAL & MECHANICAL CHARACTERISTICS
Flame Tests | Insulation Integrity | Smoke Density | Corrosive Gases Measurement |
IEC 60332-1
IEC 60332-3-24 EN 50266-2-4 |
IEC 60331
BS 6387 C, W, Z Cat,C fire @950Co – 180 min Cat,W fire and water @ 650Co -15 +15 min Cat,Z fire and mechanical shocks @ 950Co – 15 min. EN 50200 PH 120 EN 50200(Annex E) |
IEC 61034
EN 50268 HD 606 |
IEC 60754-2
EN 50267 |
Properties Value | ||
1.5 mm2 | 2.5 mm2 | |
Max. Conductor Resistant @ 20 ºC | 12.0Ω/km | 7.4 Ω/km |
Min. Insulation Resistant @ 0 ºC | 200 MΩxkm | |
Operating Voltage | 300/500 V | |
Test Voltage | 2000 V | |
Temperature Rating (Fixed) | -30 ºC to + 90 ºC | |
Temperature Rating (Flexing) | -5 ºC to + 60 ºC | |
Min. Bend Radius (Fixed) | 8 x D | |
Min. Bend Radius (Flexing) | 15 x D |
FIRE RESISTANT CABLE PH 120 SFR INSULATION
PHYSICAL INFORMATION
Nom. Cond. Cross-Sect. mm2 | Conductor Size no./mm | Earth Wire Size no./mm | Cable diameter mm (±5 %) | Weight Kg/km |
2 x 1.5 | 1/1.37 | 1/0.80 | 8.00 | 98.0 |
2 x 2.5 | 1/1.75 | 1/0.80 | 9.70 | 148.0 |
The key to our success is ,Good Product Quality, Reasonable Price and Efficient Service, for NHXH-FE 180/E 90 Installation 4×1.5mm2 fire alarm safety Cable, Halogen-Free, 0.6/1 kV, With Improved Fire Characteristics, We welcome you to inquire us by call or mail and hope to build a successful and cooperative relationship.
–
–