We thinks what customers think, the urgency of urgency to act in the interests of a customer position of principle, allowing for better quality, lower processing costs, prices are more reasonable, won the new and old customers the support and affirmation for addressable fire alarm cable,afc fire alarm cable,aquaseal fire alarm cable,we have built a reliable reputation among many customers. Quality&customer first are always our constant pursuit. We spare no efforts to make better products. Look forward to long-term cooperation and mutual benefits!
LPCB 2 Wire Conventional Photoelectric wholesale Cigarette Smoke Detector edwards fire alarm cable specification
CABLE CONSTRUCTION
Conductor
|
Screen
|
Sheath Color
|
Solid bare Copper
IEC 60228 class 1 |
Aluminium laminated polyester tape | Red ( RAL 3000) or White |
Insulation
|
Earth Wire
|
Standard Packing Mode
|
Fire resistant silicon rubber (HD 22.1, BS 7655 EI2) | Tinned Copper to IEC 60228 Solid 0.80mm |
100 mtr / Plywood Reel 500 mtr / Plywood Reel (optional)
|
Insulation Colour
|
Sheath
|
|
2 Core: blue/brown | HFFR EN 50290-2,BS 7655 LTS1/LTS3 VDE 0207 |
ELECTRICAL & MECHANICAL CHARACTERISTICS
Flame Tests | Insulation Integrity | Smoke Density | Corrosive Gases Measurement |
IEC 60332-1
IEC 60332-3-24 EN 50266-2-4 |
IEC 60331
BS 6387 C, W, Z Cat,C fire @950Co – 180 min Cat,W fire and water @ 650Co -15 +15 min Cat,Z fire and mechanical shocks @ 950Co – 15 min. EN 50200 PH 120 EN 50200(Annex E) |
IEC 61034
EN 50268 HD 606 |
IEC 60754-2
EN 50267 |
Properties Value | ||
1.5 mm2 | 2.5 mm2 | |
Max. Conductor Resistant @ 20 ºC | 12.0Ω/km | 7.4 Ω/km |
Min. Insulation Resistant @ 0 ºC | 200 MΩxkm | |
Operating Voltage | 300/500 V | |
Test Voltage | 2000 V | |
Temperature Rating (Fixed) | -30 ºC to + 90 ºC | |
Temperature Rating (Flexing) | -5 ºC to + 60 ºC | |
Min. Bend Radius (Fixed) | 8 x D | |
Min. Bend Radius (Flexing) | 15 x D |
FIRE RESISTANT CABLE PH 120 SFR INSULATION
PHYSICAL INFORMATION
Nom. Cond. Cross-Sect. mm2 | Conductor Size no./mm | Earth Wire Size no./mm | Cable diameter mm (±5 %) | Weight Kg/km |
2 x 1.5 | 1/1.37 | 1/0.80 | 8.00 | 98.0 |
2 x 2.5 | 1/1.75 | 1/0.80 | 9.70 | 148.0 |
We are proud of the high customer satisfaction and wide acceptance due to our persistent pursuit of high quality both on product and service for LPCB 2 Wire Conventional Photoelectric wholesale Cigarette Smoke Detector edwards fire alarm cable specification, Create Values,Serving Customer! is the aim we pursue. We sincerely hope that all customers will establish long term and mutually beneficial cooperation with us.If you wish to get more details about our company, Please contact with us now.
–
–