Description
With a positive and progressive attitude to customerinterest, our company continuously improves our product quality to meet the needs of customers and further focuses on safety, reliability, environmental requirements, and innovation of addressable fire alarm cable,afc fire alarm cable,aquaseal fire alarm cable,If you are interested in any of our products and services, please dont hesitate to contact us. We are ready to reply you within 24 hours after receipt of your request and to create mutual un-limited benefits and business in near future.
fire alarm cable specification Shielded 2 Core Fire Alarm Cable BC CCA with CE certification
CABLE CONSTRUCTION
Conductor
|
Screen
|
Sheath Color
|
Solid bare Copper
IEC 60228 class 1 |
Aluminium laminated polyester tape | Red ( RAL 3000) or White |
Insulation
|
Earth Wire
|
Standard Packing Mode
|
Fire resistant silicon rubber (HD 22.1, BS 7655 EI2) | Tinned Copper to IEC 60228 Solid 0.80mm |
100 mtr / Plywood Reel 500 mtr / Plywood Reel (optional)
|
Insulation Colour
|
Sheath
|
|
2 Core: blue/brown | HFFR EN 50290-2,BS 7655 LTS1/LTS3 VDE 0207 |
ELECTRICAL & MECHANICAL CHARACTERISTICS
Flame Tests | Insulation Integrity | Smoke Density | Corrosive Gases Measurement |
IEC 60332-1
IEC 60332-3-24 EN 50266-2-4 |
IEC 60331
BS 6387 C, W, Z Cat,C fire @950Co – 180 min Cat,W fire and water @ 650Co -15 +15 min Cat,Z fire and mechanical shocks @ 950Co – 15 min. EN 50200 PH 120 EN 50200(Annex E) |
IEC 61034
EN 50268 HD 606 |
IEC 60754-2
EN 50267 |
Properties Value | ||
1.5 mm2 | 2.5 mm2 | |
Max. Conductor Resistant @ 20 ºC | 12.0Ω/km | 7.4 Ω/km |
Min. Insulation Resistant @ 0 ºC | 200 MΩxkm | |
Operating Voltage | 300/500 V | |
Test Voltage | 2000 V | |
Temperature Rating (Fixed) | -30 ºC to + 90 ºC | |
Temperature Rating (Flexing) | -5 ºC to + 60 ºC | |
Min. Bend Radius (Fixed) | 8 x D | |
Min. Bend Radius (Flexing) | 15 x D |
FIRE RESISTANT CABLE PH 120 SFR INSULATION
PHYSICAL INFORMATION
Nom. Cond. Cross-Sect. mm2 | Conductor Size no./mm | Earth Wire Size no./mm | Cable diameter mm (±5 %) | Weight Kg/km |
2 x 1.5 | 1/1.37 | 1/0.80 | 8.00 | 98.0 |
2 x 2.5 | 1/1.75 | 1/0.80 | 9.70 | 148.0 |
Our development depends on the advanced equipment ,excellent talents and continuously strengthened technology forces for fire alarm cable specification Shielded 2 Core Fire Alarm Cable BC CCA with CE certification,Looking to the future, a long way to go, constantly striving to become the all staff with full enthusiasm, one hundred times the confidence and put our company built a beautiful environment, advanced products, quality first-class modern enterprise and work hard!
–
–